50 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 1 Fault Messages
X 2U1A OfflineOpen 372 6P or 18P SCR RECTIFIER FAULT
(Offline Open-Circuit)
For SCR rectifiers, this fault will occur after the initial contact closure,
or during the diagnostic sequence after a start command. After the
short-circuit test described below, the drive fires each device, and
verifies that the feedback from that device went low. If the feedback
does not go low, the drive assumes the SCR must be open-circuited.
Complete a resistance check on the rectifier, including the gate-cathode resistance, the snubber and
sharing resistors.
Complete a firing check on the rectifier.
Verify the snubber circuitry, and the sharing resistors.
Verify fiber-optic cable integrity from FOI board transmitter to SCRGD board receiver.
Replace all faulty components.
X 2U1B OfflineOpen 378
X 2U1C OfflineOpen 384
X 2U4A OfflineOpen 375
X 2U4B OfflineOpen 381
X 2U4C OfflineOpen 387
X 2V3A OfflineOpen 374
X 2V3B OfflineOpen 380
X 2V3C OfflineOpen 386
X 2V6A OfflineOpen 377
X 2V6B OfflineOpen 383
X 2V6C OfflineOpen 389
X 2W2A OfflineOpen 373
X 2W2B OfflineOpen 379
X 2W2C OfflineOpen 385
X 2W5A OfflineOpen 376
X 2W5B OfflineOpen 282
X 2W5C OfflineOpen 388
XXXX 3U1B OfflineOpen 432
XXXX 3U4B OfflineOpen 435
X X X X 3V3B OfflineOpen 434
X X X X 3V6B OfflineOpen 437
X X X X 3W2B OfflineOpen 433
X X X X 3W5B OfflineOpen 436
X X X X 4U1C OfflineOpen 438
X X X X 4U4C OfflineOpen 441
XXXX 4V3C OfflineOpen 440
XXXX 4V6C OfflineOpen 443
X X X X 4W2C OfflineOpen 439
X X X X 4W5C OfflineOpen 442
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Fault Message Fault Code Description Recommended Action(s)