Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 59
Warning Messages Chapter 2
X CNV Fan3 Ctctr 342 Loss of the cooling fan. • Verify the fan contactor, fan overload and the 120V wiring to the
XIO card.
X CNV Fan4 Ctctr 343
X CNV Fan5 Ctctr 344
X CNV Fan6 Ctctr 345
X CNV Fan7 Ctctr 346
X CNV Fan8 Ctctr 347
X CMC Fan9 Ctctr 348
X CMC Fan10 Ctctr 349
X CMC Fan9 Aux 476 The specified fan was not commanded to run but its
interposing relay status indicated that the fan was turned on.
Note: This warning is used exclusively on Heatpipe drives.
• Check fan feedback wiring and confirm with the electrical
drawings. Verify that XIO is functional.
X CMC Fan10 Aux 477
X Cnv Fan3 Aux 470
X Cnv Fan4 Aux 471
X Cnv Fan5 Aux 472
X Cnv Fan6 Aux 473
X Cnv Fan7 Aux 474
X Cnv Fan8 Aux 475
XX ConductivityHigh
(C-FRAME ONLY)
37 This warning is for liquid cool drives. The drive indicates that
the measured coolant conductivity is greater than 1 S/cm
3
.
Verify that there is no debris in the coolant, and replace the de-
ionizing cartridge if necessary.
• Verify that no foreign debris has entered the system (iron piping,
non-deionized water, etc.).
• There is no immediate need for action, but be prepared to change
the de-ionizing cartridge and run the system, verifying that the
conductivity is decreasing.
X Control Pwr Loss 112 This is used in the auto-restart feature algorithm as an indicator
to tell the drive to stop gating and wait for control power to
return. This alarm is for drives engineered with a UPS option.
There has been a loss or dip in the control power feeding the
drive for more than five cycles.
• Investigate reliability of the control power.
• Be sure the drive operates as expected when there is a control
power outage (UPS must be installed).
• Be sure that the power source is active and investigate the
reliability of the source.
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Warning Message Warning
Code
Description Recommended Action(s)