62 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 2 Warning Messages
X DB GatePwrSupply 177 This warning is for the power supply to the SGCT devices in the
DB cabinet which is being monitored using the TFB and
indicates a problem with the gate power supply associated
with a particular device.
The device feedback was not correct due to power loss to the gate
driver board. This warning can also appear as a result of another
device fault in the DB cabinet.
Check the 20V input to the gate driver board. Replace the IGDPS if
necessary.
X DB High Amb Temp 359 Either the DB cabinet ambient temperature exceeds the
warning level or the DB Air flow is less than the specified
warning level.
Verify the trip and warning settings match the factory
recommended values.
Check the DB fan, air flow, TFB and DB exhaust temperature sensor
in the DB cabinet.
X DB Low Airflow 362
X DB Temp Sensor 365 The DB temperature sensor is not functioning. A warning is
issued if this happens while running and a fault is issued when
the drive is stopped.
Check TFB and resistor exhaust temperature sensor in the DB
cabinet.
X DB TFB DataError 366 The DB TFB is not functioning. Check the TFB in the DB cabinet.
X DBOvrTemperature 364 The DB exhaust temperature has exceeded the DB over
temperature warning level.
Check the DB fan, air flow, TFB and DB resistor exhaust temperature
sensor in the DB cabinet.
Verify that the trip and warning settings match the factory
recommended values.
X DBR Overload 367 Braking energy dissipated in the DB resistor exceeded the fault
threshold (in other words, 150% of DB resistor rated energy).
This is a calculated measurement and does not reflect any
physical feedback.
Verify that the DB resistor parameter settings are correct.
Verify that the DC current feedback measurement is correct.
X DBSE1Online 420 The drive detected that the diagnostic feedback from this SGCT
device on the DB side did not match the gating pattern.
After isolating the drive from medium voltage, be sure that the
device, IGDPS power supply and the fiber-optic signals are not
damaged.
Perform gating test and verify that the gating pattern is correct and
that the drive is receiving proper gating feedback.
X DBSE2Online 421
X DBSE3Online 422
X DBSE4Online 423
X DBSH1Online 424
X DBSH2Online 425
X DBSH3Online 426
X DBSH4Online 427
X DC Link Range 167 The calculated pu value (P27) of the DC link inductance is less
than the minimum recommended. For 6-pulse SCR the value is
less than 0.8 pu, for 18-pulse SCR the value is less than 0.42 pu
and for PWM rectifier drives the value is less than 0.55 pu.
Review the DC link nameplate data.
Review the motor and drive nameplate data and verify that all
parameters were entered properly.
Contact factory if the above seems OK.