Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 81
Warning Messages Chapter 2
X X X X X X U1A Online 232 INVERTER SGCT WARNING
This warning occurs if Redn Dvc Inv option is selected in
HardwareOptions1 (P141). SGCT device in the inverter section
was detected to be faulted while the drive was running. The
drive detected that the diagnostic feedback from this device did
not match the gating pattern.
• After isolating the drive from medium voltage, be sure that the
device, IGDPS power supply and the fiber-optic signals are not
damaged.
• Complete a resistance check per the instructions in the manual.
NOTE: SGCTs may not have completely shorted, and still could read
in the k range. Any devices with low suspect readings should be
changed.
• Check the LED status of the SGCT gate driver card for abnormal
readings.
• Complete a Gating Test mode check on the devices.
• Verify the associated 20V power supply is powered and active.
• Verify all the power connections to the SGCT firing card are seated
properly.
• For nuisance faults, contact the factory about extending the
diagnostic delay.
NOTE: For Redundant devices, there will be no change in the drive
operation. For N-1 drives, the drive will attempt to run at a load/
speed combination that does not exceed the voltage rating of the
remaining devices.
X X X X X X U1B Online 238
X X X X X X U1C Online 244
X X X X X X U4A Online 235
X X X X X X U4B Online 241
X X X X X X U4C Online 247
X X X X X X V3A Online 234
X X X X X X V3B Online 240
X X X X X X V3C Online 246
X X X X X X V6A Online 237
X X X X X X V6B Online 243
X X X X X X V6C Online 249
X X X X X X W2A Online 233
X X X X X X W2B Online 239
X X X X X X W2C Online 245
X X X X X X W5A Online 236
X X X X X X W5B Online 242
X X X X X X W5C Online 248
2U AirflowSensor 392 The specified airflow velocity reading is out of normal range. • Be sure that the airflow sensor is correctly plugged in and is not
damaged.
2V AirflowSensor 393
2W AirflowSensor 394
2U Ambient Loss 444 The specified ambient temperature reading is out of normal
range.
• Be sure that the onboard temperature sensor is not damaged. If an
external sensor is used, ensure that the sensor is correctly plugged in
and is not damaged.
2V Ambient Loss 445
2W Ambient Loss 446
2U High Amb Temp 436 The drive detected high ambient temperature at the specified
location.
• Verify if the warn setting (P571) matches factory recommended
value.
2V High Amb Temp 438
2W High Amb Temp 440
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Warning Message Warning
Code
Description Recommended Action(s)