Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 85
Warning Messages Chapter 2
X X 2U1A OfflineShrt 322 6P SCR RECTIFIER WARNING
This warning occurs if Redn Dvc Rec option is selected in
HardwareOptions1 (P141) and is valid only for 6P SCR drives.
This SCR device was detected to be short circuited after the
input contactor was closed or following a start command.
• After isolating the drive from medium voltage, be sure that the
device, snubber circuit, sharing resistor and the fiber-optic signal
are not damaged.
• Complete a resistance check on the rectifier, including the gate-
cathode resistance, the snubber and sharing resistors.
• Complete a firing check on the rectifier.
• Verify the snubber circuitry, and the sharing resistors.
• Verify fiber-optic integrity from SCRGD board transmitter to FOI
board receiver.
• Replace all faulty components.
NOTE: There is only the redundant option available on the rectifier,
and only on 6P drives (SCR or PWM). You cannot have N-1 operation
on the rectifier since we cannot control the line voltage.
X X 2U1B OfflineShrt 328
X X 2U1C OfflineShrt 334
X X 2U4A OfflineShrt 325
X X 2U4B OfflineShrt 331
X X 2U4C OfflineShrt 337
X X 2V3A OfflineShrt 324
X X 2V3B OfflineShrt 330
X X 2V3C OfflineShrt 336
X X 2V6A OfflineShrt 327
X X 2V6B OfflineShrt 333
X X 2V6C OfflineShrt 339
X X 2W2A OfflineShrt 323
X X 2W2B OfflineShrt 329
X X 2W2C OfflineShrt 335
X X 2W5A OfflineShrt 326
X X 2W5B OfflineShrt 332
X X 2W5C OfflineShrt 338
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Warning Message Warning
Code
Description Recommended Action(s)