Parameter setting (setup) from front panel
To access the programming menu (setup):
Prepare the controller in MAN mode, to disconnect all the steps.
From the normal measurement display, press MODE for 3 seconds to recall the main menu. SET is displayed on the main display.
Note: If you have set the password (P.21 = ON) instead of SET the display shows PAS. Set the password using ▲▼and then press MAN-AUT
to confirm
If the password is correct the unit will show OK U or OK A depending on the entered password is user or advance level. The password can be
defined with parameters P22 and P23. Factory default is 001.
If the entered password is wrong the unit will show ERR
After having entered the password, the access is enabled until the unit is reinitialized or for 2minutes without pressing any key.
After having entered the password, repeat the procedure to access the parameter setting.
–Press▲▼to select the desired submenu (BAS ADV ALA ..) that is shown on the alphanumeric display.
The following table lists the available submenus:
Code Description
BAS Access to Base menu
ADV Accesso to Advanced menu
ALA Accesso to Alarm menu
CMD Access to Command menu
CUS Access to Custom menu (non available on this version)
EXIT Exits without saving (cancel)
SAVE Exits saving modifications.
Press MAN- AUT to access the submenu.
When you are in a submenu, the main display shows the code of the selected parameter (eg P.01 ), while the numeric/alphanumeric displays at the
bottom of the screen shows the parameter value and / or description.
Press MAN- AUT to advance in the selection of items (such as scroll through parameters P.01 P02 P03… ), or press MODE to go back to the
previous parameter.
While a parameter is selected, with ▲ ▼ you can increase/decrease its value.
Backward Increment/decrement Forward
Once you reach the last parameter of the menu, by pressing MAN-AUT once more will return you to the submenu selection.
Using ▲▼select SAVE to save the changes or EXIT to cancel.
Alternatively, from within the programming, holding MAN- AUT for three seconds will save the changes and exit directly.
If the user does not press any key for more than 2 minutes, the system leaves the setup automatically and goes back to normal viewing without
saving the changes done on parameters (like EXIT).
N.B.: a backup copy of the setup data (settings that can be modified using the keyboard) can be saved in the eeprom memory of the ALPTEC.
This data can be restored when necessary in the work memory. The data backup 'copy' and 'restore' commands can be found in the Commands
menu.
2014-AT3-5-01-ANG.indd 6 20/03/14 11:46

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpes Technologies ALPTEC 3.2 and is the answer not in the manual?

Alpes Technologies ALPTEC 3.2 Specifications

General IconGeneral
BrandAlpes Technologies
ModelALPTEC 3.2
CategoryController
LanguageEnglish