EasyManuals Logo

Alpha-InnoTec RBE User Manual

Alpha-InnoTec RBE
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10 83032600bUK– Translation into English of the original German operating manual – Subject to technical change without notice.
SOLAR THERMAL ENERGY
Solar collector, actual
Current solar collector temperature
Solar tank, actual
Current solar tank temperature
Solar collector, max
The maximum solar collector temperature reached on this day
Solar tank, max
The maximum solar tank temperature reached on this day
SWIMMING POOL
Operating mode
Here you can view the current type of operation and if required change
it too (Automatic, Party, Holidays, O)
PHOTOVOLTAICS
Operating mode
Here you can view the current type of operation and if required change
it too (Automatic, Party, Holidays, O)
SETTINGS
Software version
Current version of the room control unit software.
Language
When it is started up for the rst time the room control unit is set to the
language set in the heat pump control. This language can be changed
manually if necessary and can therefore dier from the language in the
heat pump controller.
Room sensor calibration
This function can be used to calibrate the room sensor integrated in the
RBE.
COOLING
Operating mode
Here you can view the current type of operation and if required change
it too (Automatic, O)
Cooling from outdoor temperature
= AT release in the heat pump controller
If the outside temperature that has been set is exceeded, the heat pump
switches to cooling mode. This temperature is primarily dependent on
the building standard and the demand for cooling in the building
Cooling from room temperature
= RT exceeded in heat pump controller
If the set room temperature is exceeded there is a demand for cooling.
The cooling is only started if the outdoor temperature release is also
available
NOTE
Cooling mode can be released optionally according to the
Outdoor temperature
Outdoor & room temperature
. This basic setting must be made in the heat pump control
NOTE
Cooling is activated if the corresponding release temperature(s) for
the time period set in the heat pump controller (factory setting: 12h)
has(have) been exceeded.
Cooling is deactivated if the corresponding outdoor temperature release
for the time period set in the heat pump controller (factory setting: 12h)
has been exceeded.
The time period is skipped if the temperature is already 5 K above or
below the release temperature
For detailed information on this, please refer to the operating
manual of the heat pump controller.
VENTILATION
Operating mode
Here you can view the current type of operation and if required change
it too (Automatic, Party, O)
Fan level
Info on which of the 4 fan levels is active:
O
Humidity control
Reduced operation
Nominal ventilation/Party
Intensive ventilation
Intensive ventilation period
Here you can run the ventilation in maximum mode for a settable period
and therefore achieve the highest possible air exchange. After this time
has expired the heat pump is controlled once again according to the
operating modes program

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpha-InnoTec RBE and is the answer not in the manual?

Alpha-InnoTec RBE Specifications

General IconGeneral
BrandAlpha-InnoTec
ModelRBE
CategoryControl Unit
LanguageEnglish

Related product manuals