EasyManua.ls Logo

Alpha Technologies Cordex HP 48 1.2kW - Page 68

Alpha Technologies Cordex HP 48 1.2kW
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
010-619-J0 Rev B Page 58
Mounting: Modular on Cordex CXRF 48-1.2kW series shelves (options for 1RU horizontal
or 2RU vertical orientation depending on shelf)
Relay Outputs: Seven (7) Form C, 60Vdc 1A maximum
Digital Inputs: Two (2), 0 to 60Vdc
Analog Inputs: One (1) DC voltage, 0 to 60Vdc One (1) DC current, ±50mV Two (2)
temperature, 0 to 20Vdc with power source
Communication
Ports:
Ethernet RJ-45, CAN (see shelf specifications)
Recommended Signal Wire Sizes
Wire Size Range: #16 to #26 AWG (1.5 to 0.14mm2)
Temperature
Rating:
90°C (194°F)
CAUTION: TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm2) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering
information.Specifications are subject to change without notice.
Table 10: Specifications: CXCM1+ Controller (Continued) (Sheet 3 of 3)
Specifications: Basic Unit, CXCM1+

Table of Contents