P12y/EN FT/D22 Technical Guide
User Guide
Page 82/108 MiCOM P125/P126/P127
Active :65432
Group 00010
Assigning the active setting group to the output relays;
i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
4.6.5.2 Submenu Outputs Relays for P126 and P127
AUTOMAT. CTRL
Heading of AUTOMAT. CTRL menu.
To gain access to the Output Relays submenu, press 2
and 6 until the submenu is reached.
Output Relays
Heading of Output Relays submenu.
To navigate within submenu points, press 8 2. To
modify setting, press 5. Use 8 2 4 6 to scroll and set
available selections. Press 5 to confirm choice.
Trip :8765432
0000010
Assigning output signal Trip (RL1) to other output
relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I> :8765432
0100010
Assigning first alarm threshold for phase OC (I>) to
the output relays; i.e. to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tI> :8765432
1100010
Assigning first trip threshold for phase OC (tI>) to the
output relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I_R> :8765432
0000010
Assigning first trip threshold for directional phase OC
from the inverse trip zone (I_R>) to the output relays;
i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I>> :8765432
0100010
Assigning second alarm threshold for phase OC (I>>)
to other output relays; i.e. to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tI>> :8765432
1100010
Assigning second trip threshold for phase OC (tI>>) to
the output relays; i.e. to output 3, 7 & 8 (RL3, RL7 &
RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I_R>> :8765432
0000010
Assigning second trip threshold for directional phase
OC from the inverse trip zone (I_R>>) to the output
relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.