www.altronicinc.com
7
DD-40NTV DIGITAL ANNUNCIATOR
5.0 KEYPAD DESCRIPTION/FUNCTION
5.1 MENU:
This key allows the user to view/change the following:
•
Mode selection
•
Pulses per revolution
•
Overspeed value
•
Underspeed value
*
•
Pre-lube on-time
*
•
Post-lube on-time
*
•
Output switch 1
•
Output switch 2
•
Communications
•
Baud rate
*
•
Output timer 2
•
Node number
•
Programmed hours
•
Power Supply Type
5.2 UP ARROW:
This key is used to increment/modify selections and allows the user to
view the current RPM, the hourmeter reading, annunciator status, and
all of the monitored electrical voltages
*
(back-up battery, external DC
power, and CD ignition power.
5.3 DOWN ARROW:
This key is used to decrement/modify selections and allows the user to
view the current RPM, the hourmeter reading, annunciator status, and
all of the monitored electrical voltages (back-up battery, external DC
power, and CD ignition power.
5.4 ENTER:
This key allows for selected items to be saved. When pre- or post-
lubing, pressing the ENTER key will also cancel lubrication.
5.5 STOP:
This key initiates a shutdown condition and the unit will display a
status of [60]. This has precedence over all other functions.
5.6 RESET:
This key clears any faults and resets the Class B1 and B2 timers. If
the pre-lube function is active, RESET also actuates the LUB output.
*
The annunciator displays [00] if one or more points is not armed.
Once all the channels are armed, the display reads [01]. The annun-
ciator will power up in the RESET mode. The unit will not reset the
outputs if any of the Class A points are faulted.
LOOPS TO HOME SCREEN
FROM THE HOME SCREEN
BATTERY VOLTAGE
*
EXTERNAL DC POWER VOLTAGE
*
CD IGNITION SHUTDOWN LEAD VOLTAGE
*
PRESS
I: 1 86.2
2 4.3
8:
3.6
6:
01
PRESS
PRESS
PRESS
PRESS
00056
100 3
PRESS
RPM
HOURS