- 4 - M series
Output Voltage and Stand-by Specification Charts:
AL300ULM
Output Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery ON
Stand-by = 2.5A
Alarm = 2.5A
Stand-by = 1.0A
Alarm = 2.5A
Stand-by = 300mA
Alarm = 2.5A
24VDC/12AH Battery OFF -----------------------------------------
Stand-by = 200mA
Alarm = 2.5A
-----------------------------------------
24VDC/40AH Battery OFF
Stand-by = 2.5A
Alarm = 2.5A
Stand-by = 1.0A
Alarm = 2.5A
Stand-by = 300mA
Alarm = 2.5A
AL400ULM
Output Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery ON
Stand-by = 4.0A
Alarm = 4.0A
Stand-by = 1.0A
Alarm = 4.0A
Stand-by = 300mA
Alarm = 4.0A
24VDC/12AH Battery OFF -----------------------------------------
Stand-by = 200mA
Alarm = 3.0A
-----------------------------------------
24VDC/40AH Battery OFF
Stand-by = 3.0A
Alarm = 3.0A
Stand-by = 1.0A
Alarm = 3.0A
Stand-by = 300mA
Alarm = 3.0A
AL600ULM
Output Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery ON
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
24VDC/12AH Battery OFF -----------------------------------------
Stand-by = 200mA
Alarm = 3.0A
-----------------------------------------
24VDC/40AH Battery OFF
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
AL1012ULM
Output
12VDC/12AH Battery 15 Minutes of Stand-by @ 10A
AL1024ULM
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
5 min. of Alarm
60 hr. of Stand-by &
5 min. of Alarm
24VDC / 12AH Battery
Stand-By = 8A
Alarm = 10A
Stand-By = 1.5A
Alarm = 10A
Stand-By = 130mA
Alarm = 10A
Stand-By = 30mA
Alarm = 10A
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
15 min. of Alarm
60 hr. of Stand-by &
15 min. of Alarm
24VDC / 65AH Battery -----------------------------------------------
Stand-By = 7.9A
Alarm = 10A
Stand-By = 1.4A
Alarm = 10A
Stand-By = 430mA
Alarm = 10A
For Access Control use - 24V, 8A [including 0.07A MOM5_S module current draw and 0.05A
AL1024ULXB2 power supply module current draw].