Nexto Logger
Nexto Series
NL717
CE117100 Rev. B
Current Input Mode
Input ranges Range Engineering Scale Resolution
0 to 20 mA 0 to 30.000 5,12 µA
4 to 20 mA 0 to 30.000 5,12 µA
Precision ±0,3 % of full scale @ 25
C
± 0,015 % of full scale /
C
Over scale 3 % of full scale
Maximum input current 30 mA
Input impedance 270
Configurable parameters Signal type per input
Filters
Open Channel
Low pass filter time constant 100 ms, 1 s, 10 s or disabled
Table 13: Analog Input Characteristics - Current
Note:
Input ranges: : When configured as 4 to 20 mA, input signals lower than 4 mA will result in negative values (-7,500 for 0
mA). In MasterTool IEC XE, there is a parameter called Open Loop Value was included to select the behavior in this situation.
The default value is Disabled (which provides a linear reading as described above), having also the option to provide a fixed
reading equal to lower and upper limits ("0" or "30000").
9