Cooling


GUIDE INDICATE


System will not start
Compressor will not start - fan runs
Compressor and Condenser Fan will not start
Evaporator fan will not start
Condenser fan will not start
Compressor runs - goes off on overload
Compressor cycles on overload
System runs continuously - little cooling
Too cool and then too warm
Not cool enough on warm days
Certain areas to cool others to warm
Compressor is noisy
Low suction pressure
Low head pressure
High suction pressure
High head pressure


Power Failure Test Voltage
Blown Fuse
Impact Fuse Size & Type
Loose Connection
Inspect Connection - Tighten
Shorted or Broken Wires
Test Circuits with Ohmmeter
Open Overload
Test Continuity of Overloads
Faulty Thermostat
Test Continuity of Thermostat and Wiring
Faulty Transformer
Check Control Circuit with Voltmeter
Shorted or Open Capacitor
Test Capacitor
Internal Compressor Overload Open
Test Continuity of Overload
Shorted or Grounded Compressor
Test Motor Windings
Compressor Stuck
Use Test Cord
Faulty Compressor Contactor
Test Continuity of Coil and Contacts
Faulty Fan Relay Test Continuity of Coil and Contacts
Open Control Circuit Test Control Circuit with Voltmeter
Low Voltage
Test Voltage
Faulty Evaporator Fan Motor
Repair or Replace
Shorted or Grounded Fan Motor
Test Motor Windings
Improper Cooling Anticipator Check Resistance of Anticipator
Shortage or Refrigerant Test For Leaks, Add Refrigerant
Restricted Liquid Line
Replace Restricted Part
Undersized Liquid Line Replace Line
Undersized Suction Line Replace Line
Not Enough Air across Indoor Coil Speed Blower, Check Duct Static Pressure
Too Much Air across Indoor Coil Reduce Blower Speed
Overcharge of Refrigerant
· Recover Part of Charge
Noncondensibles Recover Charge, Evacuate, Recharge
Recirculation of Condensing Air
Remove Obstruction to Air Flow
Infiltration of Outdoor Air
Check Windows, Doors, Vent Fans, Etc.
Improperly Located Thermostat
Relocate Thermostat
Air Flow Unbalanced Readjust Air Volume Dampers
System Undersized
Refigure Cooling Load
Broken Internal Parts
Replace Compressor
Broken Valves Test Compressor Efficiency
Inefficient Compressor
Test Compressor Efficiency
High Pressure Control Open Reset and Test Control
Unbalanced Power, 3PH
Test Voltage
Wrong Type Expansion Valve Replace Valve
Expansion Valve Restricted
Replace Valve
Oversized Expansion Valve
Replace Valve
Undersized Expansion Valve Replace Valve
Expansion Valve Bulb Loose Tighten Bulb Bracket
Inoperative Expansion Valve
Check Valve Operation
Loose Hold-down Bolts Tighten Bolts
No Cooling


P re ssu re s


NOTICE



Questions and Answers: