SS-DPTAC www.amana-ptac.com 8
8 www.amana-ptac.com SS-DPTAC
SPecification SHeet
SPecification SHeet
Amana
®
is a trademark of Maytag Corporation and used under license to Goodman
Company, L.P. All rights reserved. Our continuing commitment to quality products may
mean a change in specications without notice.
Copyright © 2007 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.
framing for acceSSory Wall Sleeve (WS900d)
Wall Sleeve Opening Height
Should Be Squared with
Wall Sleeve Opening Width
H = 16¼"
W = 42¼"
Fastening Wall Sleeve
When installed in an opening, the Wall Sleeve must be horizontally level
(side-to-side) and pitched ¼ bubble to the outside. (NOTE: To ensure
unit’s maximum efciency, DO NOT over- or under-pitch.)
Installation Notes
1. If Sub-base (PTSB***E) is installed, allow minimum 3¼” height
clearance and maximum 5” height clearance between wall sleeve
and oor; allow minimum 2¾” protrusion from a nished wall. See
Note 4 if using hydronic units.
2. Drain Kit (DK900D) shipped separately. Can be mounted either right
side, left side or bottom of sleeve. If mounted to bottom of sleeve,
allow 2” height clearance from oor to bottom of sleeve.
3. For UL approval, 265V units must use Amana
®
brand Sub-base
(PTSB***E) or Amana
®
brand Hard Wire Kit (PTPWHWK4).
Overcurrent protection on 265V units must be by cartridge-style
time delay fuses, which are included and factory-installed on
the Amana
®
brand 265V chassis.
4. If Hydronic Kit (HWK03 or HVK03) is installed, Wall Sleeve must
extend exactly 3" into the room from the nished interior wall. If
using the Amana
®
brand Sub-base (PTSB***E), only the minimum
3¼” height clearance between wall sleeve and oor is permissible.
Unit must also be operated with a remote-mounted thermostat.
5. If Duct Kit (MDK02B) is installed, allow a minimum of 2⅜” into the
room from the nished interior wall.
unit WitH acceSSory Wall Sleeve and
SuB-BaSe acceSSory
Top View
Right View
Wall Sleeve must extend a minimum of ¼” beyond outside wall to allow for
proper caulking.
Front View
58” LCDI CORD SET — 230V/208V UNIT*