PROGRAMMING
6
The display will show:
This function will display the walk-in temperature which will determine when the door frame heater will start.
Set the air temperature inside the walk-in at which the door frame heater will start.
To do so press to increase or to decrease the flashing value representing the air temperature.
Press when done.
The display will show:
(Default value for coolers)
(Default value for freezers)
This function will set the door frame heater temperature.
Press or to change the door frame heater temperature (the flashing value).
Once the door frame heater temperature reaches this setting, it will stay close to the set point according to the
factory set differential. Note: Set the door frame heater temperature between 75
0
F and 120
0
F.
Press when done.
The display will show:
(Default value for coolers)
(Default value for freezers)
Press or to set the percentage (flashing value) of the 4 minute cycle which the door frame
heater will stay on. The remaining time left of the 4 minute cycle the door frame heater will be off. This cycle
will repeat for as long as the controller is on.
See the examples below:
Ex1: If the flashing value is set 75P (75%), the door frame heater will run for 3 minutes and it will be off for 1
minute. This cycle will repeat for as long as the controller is on.