General safety warning about qualified personnel and potential hazards during installation.
Warning about severe injury or death from electrical shock. Emphasizes disconnecting power.
Details on R-410A refrigerant pressures and POE oil's hygroscopic nature.
Caution about high pressure refrigerant and the need to relieve pressure before opening.
Warning about abrupt system charge release when operating service valves.
Instructions for brazing refrigerant lines to service valves and filter driers.
Pressurizing lines with nitrogen and checking for leaks with a soapy solution.
Evacuating the system to below 350 microns and verifying the vacuum.
Step-by-step guide to opening the gas service valve correctly.
Detailed instructions for opening the liquid service valve carefully.
Worksheet to calculate refrigerant charge adjustments using line length and lift.
Subcooling is the recommended method for charging above 55°F ambient.
Locate design subcooling from nameplate and adjust refrigerant per charts.
Adjusting refrigerant to match liquid gage pressure with the charging chart.
Using system pressure curves to verify typical unit performance.