28
A01-00104 Rev A
Output Fuse Rating Chart
Work to be done only by qualied service personnel. It is critical that the
same type and rating of fuses are used:
Replace with same type and rating of fuse
fuse must be rated to IEC 60127-2
Model Fuse rating (slow-blow)
ABCE702-11R / ABCE702-11RMED 250 VAC 6.3 A
ABCE702-22R / ABCE702-22RMED 250 VAC 3.15 A
ABCE1002-11R / ABCE1002-11RMED 250 VAC 8 A
ABCE1002-22R / ABCE1002-22RMED 250 VAC 5 A
ABCE1442-11R / ABCE1442-11RMED 250 VAC 12.5 A
ABCE1442-22R / ABCE1442-22RMED 250 VAC 6.3 A
Technical Support
The Company provides technical product support during our regular
business hours of 8:00 a.m. to 5:00 p.m. Between the hours of 5:00 p.m.
and 8:00 a.m., our phone system will allow you to leave a message for
our technical support department. The phone mail system also provides
an emergency number to call in the event you should require immediate
assistance. In North America, call toll free at (800) 369-7179. Contact our
European headquarters at +44 (0) 1793-553980 or visit our website at www.
powervar.com for more locations.