Sequoia / Tahoe Series User Manual California Instruments
164 M447352-01 REV-A
PONS The PONS menus allow setting the conditions that would be
present after power up; The AC input must be cycled off/on for a
change in a PONS setting to take effect. The functions and
parameters have the same programmability as described in the
menus of the OUTPUT PROGRAM screen.
CAUTION!
The PONS menus allow selecting that the output would be turned on and programmed
to a high voltage when the unit is initially powered up. Ensure that suitable protection is
provided to prevent accidentally energizing the load. The factory-default setting is with
the output off and programmed to zero to provide the safest start-up condition.
PONS Menu-1
PONS Menu-2
Figure 5-104. CONFIGURATION Menu, PONS Menu-1/2
The PONS menu has the following fields:
Entry Description
PONS VOLTAGE PONS menu: Sets the value of the output voltage; the default is
zero.