Sequoia / Tahoe Series User Manual California Instruments
168 M447352-01 REV-A
Figure 5-113. PONS Voltage Sense Settings
PONS CLOCK CONFIG PONS menu: Configures the synchronization of the output
frequency and phase, dependent on whether the unit is operating
Standalone (also applicable to the Leader of a parallel group), as
a Leader of a multi-phase group, or as an Auxiliary of a multi-
phase group:
Standalone: Derives synchronization from either the user
interface SYNC signal or the internal waveform generator (with
full frequency resolution), as selected in the PONS CLOCK mode
menu (either Internal or SYNC).
Leader: Derives synchronization from either the user interface
SYNC signal or the internal waveform generator (with internal
synchronization, the phase programming resolution is limited to
1 Hz), as selected in the PONS CLOCK mode menu (either
SYNC or Internal); this setting is available only with the
Clock/Lock option, LKM; for multi-phase operation, the Leader
unit must have the setting at Leader.
Auxiliary: Derives synchronization from either the internal
waveform generator or the external Clock/Lock interface (with
external synchronization, the phase programming resolution is
limited to 1 Hz), as selected in the PONS CLOCK mode menu
(either Internal or External); this setting is available only with the
Clock/Lock option, LKS; for multi-phase operation, the Auxiliary
unit must have the setting at Auxiliary.
Figure 5-114. PONS Clock Config Settings