ANALOG   Selects the reference that determines the output voltage 
waveform and amplitude; the default is INT. The options are as 
follows: 
  INT: Selects programming of the output voltage waveform and 
amplitude by the internal controller reference. 
RPV: Selects programming of output voltage amplitude with an 
external analog interface signal, with the waveform being set by 
the internal controller reference. A Voltage field is provided for 
entry of DC input signal range: user-selectable maximum range 
value within 2.5 VDC to10 VDC, for full-scale RMS of the 
internally programmed output voltage waveform.
 
EXT: Selects programming of the output voltage waveform and 
amplitude with an external analog interface signal. A Voltage field 
is provided for entry of AC or DC input signal range: 0V to 
user-selectable maximum range value within 2.5 V(PK) to 10 
V(PK), corresponding to the maximum range of 1.77 V(RMS) to 
7.07 V(RMS), for zero to full-scale RMS output voltage; with AC 
waveform, from 16 Hz to 5 kHz (option dependent).  
NOTE: External Reference is not supported in eLOAD Mode. 
 
Figure 5-240. CONTROL INTERFACE Menu, ANALOG Sub-
Menu 
 
Figure 5-241: ANALOG Sub-Menu for eLoad-Current 
Programming Mode