What to do if the Ampac Control Panel earth fault LED is illuminated?
- AAmanda HerreraSep 9, 2025
If the Earth Fault LED is illuminated, check all input and output cabling and wiring assemblies for shorts to ground.
What to do if the Ampac Control Panel earth fault LED is illuminated?
If the Earth Fault LED is illuminated, check all input and output cabling and wiring assemblies for shorts to ground.
What to do if the Ampac ZoneSense Plus Control Panel warning system fault LED is illuminated?
If the Warning System Fault LED is illuminated, verify that the correct E.O.L. is fitted and that the wiring is connected correctly.
How to fix alarm fault on Ampac ZoneSense Plus?
To address an alarm fault, ensure you have a 10K Ohm EOL resistor fitted and a diode (1N4004) in series with the sounder.
Zones | 8 zones |
---|---|
Sounder circuits | 2 sounder circuits |
Users | 50 users |
Humidity Range | Up to 95% RH, non-condensing |
Certifications | EN54-2, EN54-4 |