8 Appendix: Approximate Back-up Time Table
Model Load (W) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24Vdc 200Ah (min)
3.2KW
300 449 1100
600 222 525
900 124 303
1200 95 227
1500 68 164
1800 56 126
2100 48 108
2400 35 94
2700 31 74
3200 28 67
Model Load (W) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
5KW
500 613 1288
1000 268 613
1500 158 402
2000 111 271
2500 90 215
3200 76 182
3500 65 141
4000 50 112
4500 44 100
5000 40 90
Note: Backup time depends on the quality of the battery, age of battery and type of battery.
Specifications of batteries may vary depending on different manufacturers.