Warning about potential injury from monitor rotation and entrapment.
Determining required clearance for monitor mounting based on oscillation and elevation.
Flushing the supply pipe before connecting the monitor to remove debris.
Specifies the maximum allowable inlet pressure for the monitor.
Describes the monitor inlet flange, required mating flange, and securement bolts.
Information on ANSUL Support Stand or other support for monitor operating force.
Caution regarding severe personal injury from moving parts in the oscillating mechanism.
Connecting a garden hose to the back of the oscillating mechanism enclosure.
Setting the selector valve handle to the TEST/MANUAL position.
Supplying water to the garden hose for testing procedures.
Checking oscillation within limits and referencing adjustment pages.
Stopping the water supply to the garden hose after testing.
Returning the selector valve handle to the RUN position and securing it.
Manually rotating the monitor to click into position.
Applying silicone grease into open ports on the underside of the oscillating valve.
Manually rotating the monitor to the opposite side until it clicks.
Applying silicone grease again to each open port.
Manually rotating the monitor back to its initial position.
Pulling the release pin to disengage the monitor from the oscillating mechanism.
Rotating the monitor 360 degrees to check for free movement.
Notice to mark or measure elevation to maintain it after testing.
Adjusting WOM-3 elevation, tightening handle, and replacing seal.
Adjusting WOM-4 elevation, tightening handwheel, and replacing seal.
Realigning holes and inserting release pin to engage monitor base.
Warning about severe personal injury from discharge stream and personnel in path.
Caution regarding severe personal injury from moving parts in the oscillating mechanism.
Operating the monitor in automatic oscillation mode by turning on the main water supply.
Adjusting stream elevation for WOM-3 (tiller bar) and WOM-4 (handwheel).
Setting up manual operation by turning the selector valve to TEST/MANUAL.
Pulling the release pin to disengage the monitor from the oscillating mechanism.
Using the tiller bar to manually rotate the monitor.
Adjusting manual stream elevation for WOM-3 and WOM-4 monitors.
Steps to return the monitor to its standby position after operation.
Procedure to turn off the main water supply after use.
Steps for manual operation: realign pin, return selector valve to RUN.
Returning the monitor to its desired elevation and securing handles.
Cleaning the filter element as per instructions on Page 9.
Replacing any broken or missing visual inspection seals on controls.
Ensuring monitor life and operation through regular maintenance every six months.
Conducting monitor testing procedures as detailed on Page 6.
Steps to clean the filter element by removing, cleaning, and reinstalling it.
Ensuring flange bolts are tight and monitor supports are secure.
Lubricating grease fittings by rotating the monitor to align access holes.
Lubricating monitor base and elevation couplings with monolithium grease.
Removing the cover from the oscillating mechanism enclosure.
Steps to tighten the drive chain by adjusting clevis assembly washers.
Lubricating the drive chain and sprockets with monolithium grease.
Reinstalling the cover onto the oscillating mechanism enclosure.
Recording the date of maintenance examination as per authority requirements.
Overview of adjusting oscillation speed using test or operating conditions.
Warning about severe personal injury from discharge stream and personnel in path.
Caution regarding severe personal injury from moving parts in the oscillating mechanism.
Adjusting oscillation speed using test mode, ensuring correct hose pressure.
Installing a pressure gauge to verify hose pressure for speed adjustment.
Removing plug from speed adjustment access hole on enclosure side.
Connecting garden hose to oscillating mechanism enclosure for speed adjustment.
Setting selector valve handle to TEST/MANUAL position for speed adjustment.
Turning on water supply to garden hose for speed adjustment.
Adjusting speed by turning control screw clockwise (decrease) or counterclockwise (increase).
Turning off water supply to garden hose after speed adjustment.
Returning selector valve to RUN position and securing with seal.
Removing pressure gauge, coupling, nipple and reinstalling pipe plug.
Adjusting speed during normal operation by turning the control screw.
Steps to set the monitor's arc of oscillation, referencing limits and locations.
Removing the cover from the oscillating mechanism enclosure.
Loosening front adjustment nuts and spinning them to the front end of the rod.
Loosening rear adjustment nuts and spinning them to the rear end of the rod.
Manually rotating the monitor to its right stop position.
Manually rotating the monitor to its left stop position until valve clicks.
Manually rotating monitor until brass tube is 6 3/4 inches from chassis rear.
Centering the monitor arc, with steps for adjustment if needed.
Manually rotating the monitor to the right position of the desired oscillation arc.
Sliding end-stop tube B into the front of the brass cylinder.
Spinning front adjustment nuts until they contact end-stop tube B.
Manually rotating the monitor left to the approximate center of the desired arc.
Spinning front nuts further and locking them to secure the arc.
Manually rotating the monitor to the right stop until the valve clicks.
Manually rotating the monitor left to the desired arc of oscillation position.
Sliding end-stop tube A into the back of the brass cylinder.
Spinning rear adjustment nuts until they contact end-stop tube A.
Manually rotating the monitor right to the approximate center of the desired arc.
Spinning rear nuts further and locking them to secure the arc.
Reinstalling the cover onto the oscillating mechanism enclosure.
Testing monitor oscillation by referring to Monitor Testing section.
Steps to protect the monitor from freezing in low temperatures.
Manually rotating the monitor to its right stop position.
Manually rotating the monitor to its left stop position until valve clicks.
Connecting a garden hose to the oscillating mechanism enclosure.
Immersing the hose end into a 50% ethylene glycol and 50% water solution.
Setting the selector valve handle to the TEST/MANUAL position.
Cycling the monitor to discharge ethylene glycol solution from the four-way valve.
Testing the strength of the ethylene glycol solution with a hydrometer.
Manually rotating the monitor to the center of its oscillation arc.
Returning the selector valve handle to RUN position and securing it.
Manually rotating the monitor to force ethylene glycol into the water bypass tube.
Repeating winterizing steps after any operation or test using water.