PMT - MANUAL
3 | PMT – Manual | AntecControls.com
Technical Specifications
Environmental
(Operating)
50°F to 95°F (10°C to 35°C), 0% to 95% R.H. (non-condensing)
Environmental
(Storage)
-22°F to 122°F (-30°C to 50°C), 0% to 95% R.H. (non-condensing)
Input Power 24 VAC +/- 10%, 50/60 Hz, 34 VA (external loads not included), Class 2
Inputs
1 Binary Input,
1 Binary/Analog Input,
1 SIN Input
Outputs
2 Analog Outputs (0 to 10 VDC, Max: 10 mA),
1 Dry Binary Output (Max: 24 VAC/VDC, 100 mA),
1 SIN Power Output (34 VDC, Max: 300 mA)
Display Type Capacitive Touch, 4.3 in. (109 mm) TFT/IPS, dimmable
Resolution
WVGA RGB 480px × 272px
Communication
Protocol
BACnet, SIN
BACnet
Device Type B-ASC
Communication Type MS/TP (RS-485)
Communication Speed 9600, 19200, 38400, 76800
Certification BTL
Control Priority Order
1. BACnet
2. Normal Operation
Room Pressure
Sensors (SRPS)
Environmental (Operating)
50°F to 95°F (10°C to 35°C),
0% to 95% R.H. (non-condensing)
Environmental (Storage)
-22°F to 122°F (-30°C to 50°C),
0% to 95% R.H. (non-condensing)
Input Power Powered from PMT
Range +/- 0.1 in.w.c. (+/- 25 Pa)
Accuracy 3% of reading
Pressure Tubing
96in. (2438mm) long, clear, fire-rated
5/32” ID × 9/32” OD × 1/16” W
Face Plate ABS plastic (white), Stainless Steel