b) messages and temporary errors (one time or periodic):
Code Description of the message
CodE
the mode of entering the access password to configuration parameters, chapter 8
Err
a wrong password to access the parameter configuration menu has been entered,
chapter 8
ConF
entering the parameter configuration menu, chapter 8
bLoc
- blockade of quick changes of setpoints (with parameter 68: bSET, chapter 9.1),
- blockade of other parameters (e.g. PASS , when PPro = oFF or IP addresses in DHCP
client mode),
- keypad lock with [F], [SET] keys and BIN input (chapter 7.1),
- [F]/[SET] key blocked by the active BIN input having the same function,
- quick manual mode for [F]/[SET]/BIN blocked by active (permanent) manual mode of
the output
tun1/2/3 , tuo1/2/3
implementation of the PID tuning function (step response or oscillation method),
chapter 9.4
EtP1/2/3
- error of interrupting PID tuning (chapt.9.4) or the program control due to a change in or
incorrect configuration (e.g. when the characteristics is different than heatin/cooling for
PID or servo)
- erasing the error with the [UP]+[DOWN] or [F], [SET] keys and the BIN input (chapt.7.1)
cLEA / none (when
missing)
erasing errors (one by one) or all with the function assigned to [F]/[SET]/BIN
StAr / StoP
start/stop of control with the function assigned to [F]/[SET]/BIN, chapter 7.1
SEt1 / SEt3
change of the setpoint (day/night) for outputs 1 and 3 with the [F]/[SET]/BIN function,
chapt.7.1
bLon / bLoF
keyboard lock on/off with the function assigned to [F]/[SET]/BIN, chap.7.1
hnd1/2/3 / hoF1/2/3
unconditional manual mode on/off, [F]/[SET]/BIN function, chapter 7.1
Pr-1/2/3 , PEnd
process controller function (ramping) on output 1/2/3, chapter 9.6
Stb1/2/3
STB (LATCH) alarm for outputs 1/2/3 (cleared by [F]/[SET]/BIN with the function cLEA or
start/stop)
vALc
the servo valve positioning (closing) procedure is performed (chapter 9.7)
LoAd
dEFA
recording of company parameter values (description of the procedure in chapter 8)
ErrE
potential data memory error (erased [UP]+[DOWN] at the power switch-on, with loading
company values), if the problem persists, send the device back for repair
11. SERIAL COMMUNICATION. AVAILABLE SOFTWARE AND USB DRIVERS
Communication with the controller is possible through each of the available serial interfaces (independently, i.e.
RS485, Ethernet and USB) and can be useful (or necessary) in the following situations:
- remote monitoring and recording of current measurements as well as control of the operating status and control
algorithms for outputs,
- quick configuration of parameters, including copying settings to other controllers of the same type
In order to establish long-distance communication, a connection should be made in the RS485 standard
(MODBUS-RTU protocol,
chapters 11.3 and 11.4) or Ethernet using the MODBUS-TCP (chapter 11.2) and MQTT
protocols (chapter 11.1).
When the controller (or RS485 converter) is connected to the computer for the first time via the USB port, the
system will start the process of automatic installation of the COM serial port driver (from the Windows Update
website). Alternatively, you can manually indicate the location of the driver on the computer's disk from the
Device Manager , following the instructions of the installation wizard (for the regulator, select the"AR2xx