EasyManua.ls Logo

APAR AR602.B - 4 Technical Data

APAR AR602.B
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
- by default, the controller is configured to present the temperature from the Pt100 sensor, heating type
control (ON-OFF algorithm with hysteresis) for P1/SSR1, P2/SSR2 and P3/SSR3 outputs (alarm 3),
description in chapter 9.
4. TECHNICAL DATA
Universal input (1 programmable - parameter 0: inP , 17 types, 18 bit A/C conversion), measuring ranges
- Pt100 (RTD, 3- or 2-wire) -200 ÷ 850 °C - R (TC, PtRh13-Pt) thermocouple -40 ÷ 1600 °C
- Ni100 (RTD, 3- or 2-wire) -50 ÷ 170 °C - T (TC, Cu-CuNi) thermocouple -25 ÷ 350 °C
- Pt500 (RTD, 3- or 2-wire) -200 ÷ 620 °C - E (TC, NiCr-CuNi) thermocouple -25 ÷ 820 °C
- Pt1000 (RTD, 3- or 2-wire) -200 ÷ 520 °C - N (TC, NiCrSi-NiSi) thermocouple -35 ÷ 1300 °C
- J (TC, Fe-CuNi) thermocouple -40 ÷ 800 °C - current (mA, R
in
= 50 Ω) 0/4 ÷ 20 mA
- K (TC, NiCr-NiAl) thermocouple -40 ÷ 1200 °C - voltage (V, R
in
= 110 kΩ) 0 ÷ 10 V
- thermocouple S (TC, PtRh10-Pt) -40 ÷ 1600 °C - voltage (mV, R
in
> 2 M Ω) 0 ÷ 60 mV
- B (TC, PtRh30PtRh6) thermocouple 300 ÷ 1800 °C - resistive (R, 3-p or 2-p) 0 ÷ 2500 Ω
Response time for measurements (10÷90%)
0.2 ÷ 3.5 s (programmable), default ~ 0.5 s
Leads resistance (RTD, Ω)
R
d
< 25 Ω (for each line), auto or fixed compensation
Resistance input current (RTD, Ω)
400 μA (Pt100, Ni100), 200 μA (Pt500, Pt1000, 2500 Ω)
Processing errors (at an ambient temperature of 25°C):
- basic - for RTD, mA, V, mV, Ω 0.1% of the measuring range ± 1 digit
- for thermocouples 0.2% of the measuring range ± 1 digit
- additional for thermocouples <2 ° C (temperature of cold ends)
- additional caused by ambient temperature changes <0.004 % of input range /°C
Resolution of measured temperature
0.1 °C or 1 °C, programmable (with parameter 3: dot )
Indications range (resolution for analog inputs)
maximum -1999 ÷ 9999, programmable
Decimal point position for analog inputs
programmable (3: dot) in the range of 0 ÷ 3, i.e.
0 ÷ 0.000
BIN digital input (contact or voltage <24V)
bi-state, active level: short-circuit or <0.8V
P/SSR bi-state
outputs (3
independent, P3/SSR3
not available for
AR602.B)
- relay P (P1, P2, P3), standard
for outputs 1 and 2, option for
output 3, (current for resistive loads)
AR642.B/652.B/682.B: 8A/250Vac, 1xSPDT, 2xSPST-NO
AR602.B/662.B: 5A/250Vac, 2(3 for AR662.B)xSPST-NO
AR632.B: 8A/250Vac (1xSPDT), 5A/250Vac (2xSPST-NO)
- SSR (SSR1, SSR2, SSR3), option
transistor type NPN OC, 11V, current < 35mA
Analog output
mA/V (1 current or
voltage, not
galvanically
separated from the
input)
- current 0/4 ÷ 20 mA, active
(standard)
maximum resolution 1.4 μA (14 bit)
output load Ro < 1 kΩ
- voltage 0/2 ÷ 10 V (option,
instead of 0/4 ÷ 20 mA output)
maximum resolution 0.7 mV (14 bit)
output load lo < 3.7 mA (Ro> 2.7kΩ)
- errors (% of the initial range) primary <0.1%, additional 0.004%/°C, at 25°C
Power supply (Usup, universal, compliant with the
standards 24Vac/dc, 48Vac/dc, 110Vac, 230Vac, etc.)
18 ÷ 265 Vac, <3VA (alternating voltage, 50/60Hz)
22 ÷ 350 Vdc, <4W (direct voltage)
Power supply for object transducers
24Vdc / 30mA
Communication
interfaces
(independent,
can be used
simultaneously)
- USB (micro connector type B,
communication
with a computer), standard
drivers for Windows 7/8/10 (virtual COM serial port,
MODBUS-RTU protocol, Slave)
- RS485 (separated), option (in
AR602.B excludes mA/V output and
BIN input)
MODBUS-RTU protocol, Slave, speed 2.4÷115.2 kb/s,
programmable character format (8N1, 8E1, 8o1, 8N2)