7
c) AR662.B
AR662.B
d) AR632.B
AR632.B
6. DESCRIPTION OF CLAMPING RAILS AND ELECTRICAL CONNECTIONS
Table 7. Numbering and description of clamping rails
Clamps /
Connectors
Description
1-2-3 Pt100, Ni100, Pt500, Pt1000 input, resistive, (2- and 3-wire)
2-3 thermocouple input TC (J, K, S, B, R, T, E, N) and voltage input 0÷60mV
3-5 current input 0/4÷20mA
4-5 voltage input 0÷10V
6 +24V output (in relation to 5-GND) of the built-in power supply of object transducers
5-7 BIN binary input (contact or voltage <24 V)
5-8 analog output: current (0/4 ÷ 20mA) or voltage (0/2 ÷ 10V)
9-10 (7-8 for
AR602.B), option
RS485 serial interface (MODBUS-RTU protocol), in AR602.B RS485 module excludes
analogue mA/V output and binary input BIN (according to the order code), chap.11
12-13 power supply input (universal)
14-15-16
P1 or SSR1 relay output (14-15), for AR602.B P2 or SSR2 output: 14-15
17-18
P2 or SSR2 relay output, for AR602.B P1 or SSR1 output
19-20
P3 or SSR3 relay output (except AR602. B)
USB (micro type B) USB serial interface for cooperation with a computer, chapter 11
RJ45 (option) Ethernet serial interface (MODBUS-TCP, MQTT protocols, etc.), chapter 11
Housing type
on the rail, Modulbox 3MH53
Material
PC/ABS self-extinguishing
Housing dimensions
53 x 90 x 62 mm (W x H x D, without
connectors)
Mounting on the TS35 rail (DIN EN 60715)
Cable cross-sections
(for separable
connectors)
2.5 mm
2
(power supply and P/SSR
outputs),
1.5mm
2
(other)
Housing type
industrial IP65, Gainta G2104
Material
polycarbonate
Housing dimensions
120 x 80 x 55 mm (W x H x D, without
glands)
Mounting
4 holes Φ4.3 mm, spacing 108x50 mm,
accessible after removing the front cover
Cable cross-sections
(for separable
connectors)
2.5 mm
2
(power supply and P/SSR
outputs),
1.5mm
2
(other)