ELECTRICAL CONSIDERATIONS
The intelligent refl ective beam detector is loop-
powered and requires no external power supply.
Each beam detector draws approximately 5mA
in quiescent and 9mA in alarm from the ana-
logue addressable loop and, unless proven by
calculation*, it is recommended that no more
than ten beam detectors be powered from each
loop.
*A loop voltage drop calculation program,
known as ‘Loop Calculator, has been devel-
oped by Apollo for use by system designers
and is available as a free download from the
Apollo website (www.apollo-fi re.co.uk)
LED FAULT INDICATION
A fault is indicated by the amber LED fl ashing
once a second.
If the drift compensation function has reached
its limit the amber LED fl ashes once every 2
seconds. The detector will continue to function
but maintenance procedures should be carried
out at the earliest opportunity.
PANEL COMPATIBILITY
Please note, not all control panels support this
beam detector. Please contact Apollo’s Technical
Sales department for further information.
FURTHER INFORMATION
The intelligent refl ective beam detector must be
installed in accordance with the installation guide,
PP2146. This guide contains more information on
the following topics:
• system design
installing beam detectors
targeting, aligning and commissioning
the re ective beam detector
• troubleshooting
This guide is available on request or can be down-
loaded from the Apollo website,
www.apollo- re.co.uk. If further assistance is
required, please contact the Technical Sales depart-
ment.
Technical Data
Supply Voltage 17–28V DC
(plus protocol)
Supply Current
Prism targeting mode 17mA
Alignment mode 17mA
Run mode (quiescent) 5mA
Alarm (LED illuminated) 9mA
Fault (LED illuminated) 5mA
Alarm thresholds
25% 2.50dB
35% 3.74dB
50% 6.02dB
Operating temperature 20°C to 55°C
Humidity 0 to 93%RH
(Non-Condensing)
IP rating 50
Material Flame Retardant ABS
Colour Grey/Black
Dimensions (beam detector)
Width 130mm
Height 210mm
Depth 120mm
Weight 670g
Dimensions (termination backbox)
Width 130mm
Height 190mm
Depth 50mm
Part no Description
45681-334
5–50 metres (detector to refl ector)
45681-292
50–100 metres (detector to refl ector)
45681-293
Termination backbox
For further technical information please refer to
PP2155-T, available on request.