2 3
Explosion Protection Category
All Apollo XP95 IS detectors and call points comply with the categories:
II IG Ex ia IIC T5 -20°C≤Ta≤45°C (T4≤60°C) Ga
Orbis IS detector categories are:
II IG Ex ia IIC T5 -50°C≤Ta≤40°C (T4≤60°C) Ga
The ATEX EC type examination certificate numbers applicable to Apollo IS devices are
given in the table below:
ATEX Certificate Apollo Product
BAS02ATEX 1289X XP95 IS Detectors
BAS02ATEX 1290X XP95 IS Call Points
Baseefa 06 ATEX 0007X Orbis Detectors
IECEx Certificate
IECEx BAS 12.0091X XP95 IS Detectors
IECEx BAS 12.0091X XP95 IS Call Points
IECEx BAS 06.0002X Orbis Detectors
Copies of all component and system certificates, and system drawings are available from
Apollo on request.
Installation of Detectors
Detectors must be fitted to certified IS bases. Use of any other bases will invalidate the
detector certification. Orbis detectors may be fitted to Series 60 systems using an Orbis IS
base adaptor.
The bases must be installed in such a way that all wiring is protected to at least IP20. This
requirement will be met if bases are flush mounted. If bases are mounted on BESA boxes, or
other boxes having a diameter less than 85mm, they should be fitted with XP95 backplates
(Apollo part number 45681-233).
Remote LED indicators may be fitted to Orbis or to XP95 detectors. The LEDs need not be
certified but should be either 3mm or 5mm in diameter. The LED terminations must be
protected to at least IP20 and the circuits must be segregated from other circuits.
Special Conditions for Safe Use
To avoid problems with electrostatic charging of the enclosure, the equipment must not be
located in a dust-laden airflow or cleaned with a dry cloth or with solvents.
Installation of Manual Call Points
Manual call points must be installed to comply with the requirements of the ATEX directive
or another applicable code of regulations. All unused cable entry ports must be sealed
using suitable stopping plugs to give the required level of ingress protection.
Dust Cover
To ensure optimal performance, leave the dust cover on the product and remove on
commissioning.
Further Information
For further information see Apollo publications PP1095 for the XP95 ranges respectively. For
information on Orbis see publication PP2250
See also www.apollo-fire.co.uk/resources/ATEX
ATEX en français, Deutsch, Italiano, Español, Česky, slovenšèina, Svenska, Nederlands,
português, Ελληvικά, Suomi, Dansk, Magyar, Polski, Lietuvių kalba, Eesti, Latviešu, slovenský
jazyk
Apollo Fire Detectors Ltd Declaration of Conformity
Notified Body for EC Type Examination and Production: Fimko 0598, Helsinki, Finland
Harmonised Standards used: EN60079-0:2018 Electrical Apparatus, Explosive atmospheres. Equipment.
General requirements and EN60079-11:2012 Electrical Apparatus, Explosive atmospheres. Equipment
protection by intrinsic safety ‘i’
Provisions of the Directive fulfilled by the Equipment :
XP95 – Group II Category 1G Ex ia IIC T5 Ga (-20°C ≤ Ta ≤ +45°C) or EEX ia IIC T4 Ga (-20°C ≤ Ta ≤ 60°C)
Orbis - Group II Category 1G Ex ia IIC T4 Ga (-50°C ≤ Ta ≤ +60°C) / T5 (-50°C ≤ Ta ≤ +40°C)
MCP – Group II Category 1G / 1D Ex ia IIC T5 Ga (-20°C ≤ Ta ≤ +45°C) or Ex ia IIC T4 Ga (-20°C ≤ Ta ≤
+60°C) or Ex ia IIIC T135°C Da (-20°C ≤ Ta ≤ +60°C)
The products listed below are manufactured at the premises of
Apollo Fire Detectors Ltd., 36 Brookside Road, Havant, Hampshire, PO9 1JR, England.
Product
Name
Models Covered
EC type Examination
Certificate
Derived from
Un-configured
Platform
Orbis IS Multisensor
Baseefa06ATEX0007X/5
Issued 22 April 2020
400-OH-00012
Orbis IS Optical Smoke Detector
Baseefa06ATEX0007X/5
Issued 22 April 2020
400-OP-00013
Orbis IS
Heat Detector
A1R /A1S/A2S/BR/BS/CS
Baseefa06ATEX0007X/5
Issued 22 April 2020
400-HT-00011
XP95 IS Heat Detector 55000-440
BAS02ATEX1289X/8, Issued 19 March 2020,
IECEx BAS 12.0091X
XP95 IS
Optical Smoke Detector
55000-640
BAS02ATEX1289X/8, Issued 19 March 2020,
IECEx BAS 12.0091X
XP95 IS
Ionisation Smoke Detector
55000-540
BAS02ATEX1289X/8, Issued 19 March 2020,
IECEx BAS 12.0091X
XP95 IS
MCP
Manual Call Point
55100-940, 55100-942, 55100-944
BAS02ATEX1290X/12, Issued 19 March 2020,
IECEx BAS 12.0091X
XP95 IS
MCP
MEDC Manual Call Point
55000-960, 55000-961, 55000-962, 55000-963,
55000-964, 5500-965, 55000-966, 55000-967
BAS02ATEX1290X/12, Issued 19 March 2020,
IECEx BAS 12.0091X
XP95 IS
MCP
Push Button Manual Call Point
55000-970, 55000-971, 55000-972, 5500-973
BAS02ATEX1290X/12, Issued 19 March 2020,
ECEx BAS 12.0091X
XP95 IS
MCP
55200-940, 55200-942, 55200-944
BAS02ATEX1290X/12, Issued 19 March 2020,
IECEx BAS 12.0091X
Directives also applicable: Electromagnetic Compatibility 2014/30/EU; Construction Products
Regulations 305/2011/EU; Marine Equipment Directive*, European Directive On Equipment and
Protective Systems Intended for the use in Potentially Explosive Atmospheres**.
*This declaration is valid for Directive 96/98/EC as amended by 2015/559 until 17 September 2016
*This declaration is valid for Directive 2014/90/EU from 18 September 2016
**This declaration is valid for Directive 94/9/EC until 19 April 2016
**This declaration is valid for Directive 2014/34/EU from 20 April 2016
This Directive has been enacted into the UK law by the Statutory Instrument No. 1996-192, The Equipment
and Protective Systems Intended for the Use in Potentially Explosive Atmospheres Regulations 1996.
On behalf of the above named company, I declare that, on the date the equipment accompanied
by this declaration is placed on the market, the equipment conforms with all technical and regulatory
requirements of the above listed directives. Both Software and Electronics Team Leader, Mr Rob Knight,
and Systems Engineer, Mr Mark Schofield have been designated as the responsible person(s) for the
purpose of the Regulations.
..................................................... Havant, 22/04/2020 .................................................... Havant, 22/04/2020
Mr Rob Knight Mr Mark Schofield
Software and Electronics Team Leader Systems Engineer