ALD-100 ELECTRONIC
REFRIGERANT LEAK DETECTOR
Read this manual before using this product.
Failure to do so can result in serious injury.
WARNING
RESET
ON
OFF
ALD-100
Leak detector x 1 Flexible probe x 1
Sensing tips x 2 C batteries x 2
Aluminum case x 1 User Manual x 1
2. Automatic Circuit.
When the unit is first powered on, it will set itself to ignore the current level of
halogen in the atmosphere. This allows the unit to identify leaks by the higher
concentration of halogen present at the leak location.
- ApplicationR12, R11, R500, R22, R123, R124, R502, R134a, R404a, R125
refrigerants and blends such as HP62 and MP39.
- Operating temperature: 0 °C - 52 °C (30°F- 125°F)
- Maximum sensitivity: 3 g/yr., for all halogenated refrigerants
- Battery life: approx. 50 hours of normal use
- Response time: instant
- Work mode: continuous, no limitations
- Fixed probe length: 14 in
- Dimension: 9 x 2.5 x 2.5 in
- Power supply: 2C Alkaline batteries
Specifications
Packing List
Technical Specifications Video Instruction
Notices
- Do not let children handle the product, keep them away from the working
area.
- Do not submerge the product in water.
- Do not expose the product to temperatures exceeding 60°C.
- Do not leave the product in direct sunlight for long periods of time.
- Do not dismantle or attempt repairs of the product without authorization.
- Remove the batteries when not used for extended periods of time.
- Keep the sensing tip clean from dust, moisture and grease.
- If dirty, clean the tip by immersing in mild solvent such as alcohol for
several seconds then using compressed air or a towel to dry.
- Do not use solvents such as gasoline, turpentine minerals etc. to clean the
product.
- Turn the tool off before replacing the sensing tip to avoid mild electric
shock.
sales@aprvtiotech.comhttps://aprvtiotech.com/ +1 713 701 1986 sales@aprvtiotech.comhttps://aprvtiotech.com/ +1 713 701 1986
Question and Answer IconNeed help?

Do you have a question about the APRVTIO ALD-100 and is the answer not in the manual?

APRVTIO ALD-100 Specifications

General IconGeneral
BrandAPRVTIO
ModelALD-100
CategorySecurity Sensors
LanguageEnglish

Summary

Automatic Circuit Operation

Unit Initialization

When powered on, the unit self-calibrates to ignore ambient halogen levels for accurate leak detection.

Product Specifications and Contents

Application and Operating Parameters

Lists compatible refrigerants, operating temperature range, maximum sensitivity, and battery life.

Packing List

Details all items included in the product package, such as the detector, probes, and user manual.

Usage Guidelines and Safety Notices

Important Safety Precautions

Provides critical warnings regarding product handling, water exposure, temperature limits, and maintenance.

Device Features and Setup

Main Features

Highlights key functionalities including refrigerant detection, sensitivity levels, and alarm indications.

Operational Tips

Offers guidance on adjusting sensitivity, resetting the unit in contaminated areas, and dealing with windy conditions.

Sensitivity and Alarm Indicators

Explains the seven sensitivity levels and eighteen alarm levels, detailing LED color and pattern changes.

Setup and Operation Steps

Provides a step-by-step guide for powering on, checking battery, adjusting sensitivity, and searching for leaks.

Battery and Reset Functions

Details the battery level indicator and the procedure for resetting the unit to zero for recalibration.