2-2. Embedding the Tubing and Wiring
Before beginning embedding installation work, con-
sult fully with agencies or offices related to the build-
ings foundation, construction, electricity, and water.
Wait to make connections to the embedded portion.
Each connection step is described later in this
manual.
Securely cover the end of the embedded tubing to
prevent intrusion of dirt or moisture.
If an embedded tube is to be left for a long time, fill
the tube with nitrogen and seal both ends securely.
If a tube is left open for an extended time, moisture
in the air inside the tubing may condense into water
droplets, and lead to water contamination of the
refrigerant circuit.
In order to prevent insulation breakdown and ground
faults, do not allow wiring ends to come in contact with
rainwater, or be subjected to condensation or dew.
Apply sufficient thermal insulation to the refrigerant
tubing and drain pipes.