1X-F Series Operation Manual 11
Battery power and battery fuse fault indication:
General Fault LED: Flashing.
Supply Fault LED: Flashing.
Control panel buzzer: Sounding intermittent.
Earth fault indication
General Fault LED: Flashing.
Earth Fault LED: On steady.
Control panel buzzer: Sounding intermittent.
Note: Contact your installation or maintenance contractor to investigate the
cause of all reported faults.
Disablements
Disabled zones are indicated as follows:
General Disable LED: On steady.
Corresponding Zone LED: On steady yellow.
Control panel buzzer: Off.
Disabled sounders (or evacuation for NBN S 21-100) are indicated as follows:
General Disable LED: On steady.
Sounder LED: On steady yellow.
Control panel buzzer: Off.
Disabled fire routing (or warning for NBN S 21-100) is indicated as follows:
General Disable LED: On steady.
Fire Routing LED: On steady yellow.
Control panel buzzer: Off.
Disabled expansion boards are indicated as follows:
General Disable LED: On steady.
I/O LED: On steady yellow.
Control panel buzzer: Off.
Disabled fire protection is indicated as follows:
General Disable LED: On steady.
Fire Protection LED: On steady yellow.
Control panel buzzer: Off.