1X-F Series Operation Manual 17
Operator user level operation
The operator user level is protected by password security and is reserved for
authorized users who have been trained to operate the control panel for control
and maintenance purposes. The default operator user password is 2222.
Those tasks included in the topic Public user level operationon page 14 are
also available at the operator user level.
This user level lets you:
Reset the control panel
Stop or restart sounders (or evacuation for NBN S 21-100)
Silence sounders before activation
Start sounders in evacuation mode of operation
Enable or disable a configured sounder delay (or evacuation delay for
NBN S 21-100)
Enable or disable a configured fire routing delay (or warning delay for
NBN S 21-100)
Enable or disable a configured extended fire routing delay
Test a zone [1]
Disable or enable a zone [1]
Test sounders (or evacuation for NBN S 21-100)
Disable or enable sounders (or evacuation for NBN S 21-100) [1]
Test fire routing (or warning for NBN S 21-100)
Disable or enable fire routing (or warning for NBN S 21-100) [1]
Disable or enable other features (all expansion boards, fire protection and
fault warning outputs)
[1] These operations can be performed when the control panel is in alarm.
Resetting the control panel
Note: Investigate all alarms and system faults before resetting the control panel.
To reset the control panel and clear all current system events, press the Reset
button. System events that have not been resolved continue to be highlighted
when the reset process ends.

Other manuals for Aritech 1X-F Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 1X-F Series and is the answer not in the manual?

Aritech 1X-F Series Specifications

General IconGeneral
BrandAritech
Model1X-F Series
CategoryControl Panel
LanguageEnglish

Related product manuals