1X-F Series Operation Manual 19
Enabling or disabling a configured sounder delay (or evacuation delay for
NBN S 21-100)
To enable a configured sounder delay (or evacuation delay for NBN S 21-100),
press the Sounder Delay button (or the Evacuation Delay button for
NBN S 21-100). To disable the delay, press the button again.
Note: Availability of this feature is subject to configuration and its functionality
may vary for each zone. Contact your fire system installation or maintenance
contractor to confirm your configuration details.
Enabling or disabling a configured fire routing delay (or warning delay for
NBN S 21-100)
To enable a configured fire routing delay (or warning delay for NBN S 21-100),
press the Fire Routing Delay button (or the Warning Delay button for
NBN S 21-100). To disable the delay, press the button again.
Note: Availability of this feature is subject to configuration and its functionality
may vary for each zone. Contact your fire system installation or maintenance
contractor to confirm your configuration details.
Enabling or disabling a configured extended fire routing delay
If configured, the extended fire routing delay is enabled or disabled at the same
time as the standard fire routing delay.
In NEN 2535 operating mode, the extended fire routing delay becomes the active
delay when sounders are stopped (by pressing the Sounder Start/Stop button)
and remain stopped when the standard fire routing delay time has elapsed.
In EN 54-2 Scandinavia operating modes, the extended fire routing delay
becomes the active delay when an extended fire routing delay switch is activated
while the standard fire routing delay elapses. (This delay option is also available
for EN 54-2 and NEN 2535 operating modes if configured during installation.
Contact your fire system installation or maintenance contractor to confirm your
configuration details.)

Other manuals for Aritech 1X-F Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 1X-F Series and is the answer not in the manual?

Aritech 1X-F Series Specifications

General IconGeneral
BrandAritech
Model1X-F Series
CategoryControl Panel
LanguageEnglish

Related product manuals