1X-F Series Operation Manual 21
Disabling or enabling a zone
To disable a zone, press the General Disable button, and then press the
corresponding Zone button.
A disabled zone is indicated as follows:
General Disable LED: On steady.
Zone LED: On steady yellow.
To enable the zone, press the General Disable button, and then press the Zone
button again. If a disabled zone contains a device in alarm, the zone will not be
enabled until the control panel is reset.
Notes:
If it is the only zone in alarm, no fire alarm or fault is indicated for the disabled
zone and any linked fire outputs are stopped.
If one or more zones are in alarm when the zone is enabled, the zone enters into
alarm and re-activates the stopped fire outputs.