Steam Dispersion Type:
HumidiPack ExpressPack Fan package (EHF)
Dispersion Tube Dispersion Tube with Drain
Other: ________________________________________
Serial number of dispersion type used:________________________________________
Plumbing:
Inlet Water:
Inlet water pressure between 25-120 psig
Drain Lines:
Size:_______
Air gap located within 3’ of humidifier
Line pitched 1” per 12” away from humidifier
Temp-R-Drain (condensate cooler)
Other condensate cooler: ________________________________________
Wiring:
All wires connected securely connected
No loose wires around PC board
Proper breaker and wire size per table on page 29
Control Wiring:
Installed
High Limit Humidistat
Mounted 10 feet downstream of dispesion
Air proving/pressure switch
Mounted upstream of dispersion
Modulating Humidistat/Controller
Signal Type:
0-10 VDC 4-20 mA
Communications
Modbus BACnet LonWorks