22
Fill in the right-hand column with the Set-Up Wizard settings that you use when programming the panel.
Record the setup date. If any settings change, record those changes and the date they were made.
Function Options Settings
Initial Set-Up
Setting Date
Adjusted
Setting Date
Temperature Display F/C
Mode Priority Automatic, Cooling, Heating, Zone Weight
Zone 1 T-Stat Heat Pump-
Heating/Cooling
Z1 Weight Zone 1: 10%-90%
Z2 Weight Zone 2: 10%-90%
Z3 Weight Zone 3: 10%-90%
Z4 Weight Zone 4: 10%-90%
Air Handler Stage-up Threshold 30%-100%
Heat Stage Threshold Enter Temp: 80-130
Cool Stage Threshold Enter Temp: 20-60
Balance Point-OAT Enter Temp: 0-50 of Back-up Heat
Resistance Lockout-OAT Enter Temp: Lock-In or 0 to 40
H.P. LAT High Limit Enter Temp: 100-125
AUX LAT High Temp Enter Temp: 130-180
Cooling LAT Low Temp Enter Temp: 34-46
Type of Back-up Electric/Fossil Fuel
Back-up Controls Fan True-False
Dehumidier Call Voltage 0 VAC/24 VAC
Secondary Purge Time Enter Sec: 0-180
Dehumidication Cycle Time Enter Min: 5-10-15
Cooling Low Ambient Lockout Enter Temp: 20-60
Rev Valve Energized Cooling/Heating
Use balance point for electric True-False
Demo mode enable True-False
Setup Worksheet