381333–005 B
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Installation
Manual
920
Remote Control Switches
30 th roug h 225 am pe re si ze s
DANGER is used in this manual to warn of high
voltages capable of cau si n g shock , burns, or death .
WARNINGisusedinthismanualtowarn
of possible personal injury.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
!
This Installation Manual is for green nameplate
ASCO 920s only. F or black nameplate ASCO
920s refer to Owner’s Manual 2D4920 R16.
ASCO 920 Remote Control (RC) Switches are pre–tested
and ready to use. Installation requires mounting and
connection of service cables (or bus) and control circuit
wires. An experienced licensed electrician should install
the RC Switch.
Each ASCO 920 RC Switch has a ratings / identification
label defining load types and maximum voltage ratings.
Use the switch only within the limits shown on this label.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
TABLE OF CONTENTS
page
Installation & Maintenance 1................
Troubleshooting & Parts Kits 2..............
Optional Accessories 3.....................
Wiring & Outline Diagrams back of manual...
Catalog Number Identification with Elements Explained
Typical ASCO 920 catalogno. for 3 pole, 100 amp, 208 volt 60 Hz control, with subpanel and enclosed Remote Control Switch:
920 3 100 6 1
Phase Poles
Product
Amperes
Control V ol tage
Accessories
X
3 –threephase
2 –singlephase
9 440 480 V
7 265 277 V
G 550 600 V
X other voltages
920
Enclosure
C
blank open type
C
Subpanel
0 without
30
100
150
200
225
75
60
6
208 240 V
3 110 120 V
50 60 Hz
1 –with
if
accessories
ordered
blank none

Questions and Answers

  • I
    imasonJul 26, 2025
    What to do if Asco RC Switch tries to open or close, but cannot?
    • R
      Richard JonesJul 26, 2025
      If your Asco RC Switch attempts to open or close but fails, verify the voltage to ensure the control line voltage is at least 90% of the nameplate coil voltage. Additionally, check the control line size and distance to confirm they meet the specified requirements. If a transformer is used, ensure it can handle the VA burden.
  • F
    floresscottAug 11, 2025
    Why does my Asco RC Switch open and close repeatedly?
    • A
      antonio63Aug 11, 2025
      If your Asco RC Switch is opening and closing repeatedly, examine the wiring to ensure that the control stations are not simultaneously signaling the ASCO 920 to open and close. Also, check the control station to make sure it does not have overlapping contacts.

Summary

Catalog Number Identification

Installation

Mounting

Details on mounting RC switches, including diagrams for enclosed and open-type switches.

Service Connections

Information on mechanical support and electrical connection for panelboard mounting and subpanel switches.

Control Line Connections

Instructions for connecting control circuit wires to clamp-type terminals.

Maintenance

Switch Lubrication

Guidance on relubrication, recommended lubrication kits, and conditions requiring attention.

Inspect Main Current-Carrying Contacts

Procedures for checking contact condition, replacement criteria, and handling arc chutes.

Manual Operation

Troubleshooting

Replacement Parts Kits

Optional Accessories

Pilot Lights (Accessory 9)

Details on pilot lights, their function (Acc. 9A/9B), and installation requirements.

Auxiliary Contacts (Accessory 14)

Information on auxiliary contacts (14A & 14B) for the ASCO 920, including wiring and mounting.

Two-Wire Control Relay (Accessory 47)

Details on accessory 47, an auxiliary relay panel for 2-wire control of ASCO 920.

Three-Wire Control Relay (Accessory 48)

Information on accessory 48, an auxiliary relay panel for 3-wire control of ASCO 920.

Form 3 Control Relay (Accessory 49)

Details on accessory 49, an auxiliary relay for Form 3 control of ASCO 920.

Control Line Fuses (Accessory 52)

Information on optional control line fuses (Acc. 52A, 52B, 52C) for ASCO 920 switches.