INSTALLATION
IM14229-4
GB
1.2 OPERATING ELEMENTS
1.3 OPERATING MODES
Shut-off:
If the setpoint falls below 0.5 %, the coil current is switched off and the valve is fully exhausted.
Overtemperature:
If the temperature of the internal control electronics exceeds 100°C, the operating mode is switched to AUTOSAFE.
Undervoltage / overvoltage:
If the supply voltage is less than 18 V or more than 30 V, the coil current is switched off and the valve is fully
exhausted..
Autosafe:
If the coil current exceeds a certain value, dependent on the mechanics, for more than 20 seconds, the output
current is limited to max. 70% to prevent the valve from overheating.
1 Proportional solenoid coil
2.1 Pressure supply
2.2 Pressure outlet
2.3 Exhaust
3 Power supply, M12 connector or
7-pin DIN connector
4 Ground connection M4
5 Mounting hole
6 Serial communication RS232 (PC connection)
7 LC display
8 2 pushbuttons
3
1
2.1
5
2.3
6
4
2.2
5
7
8