Galvanic insulation 500V
~
/1min.
Resol.: 12 bit (0.025%)
Accur. 0.1%. Short circuit protection
41
8 - Technical Specifications
Features
at 25 °C env. temp.
Description
Control
output
Alarms
OP4 analogue
output
(optional)
Setpoint
Whole scale
±
range
1A/250V
~~
resistive loads
0…1/5/10V
500Ω / 20mA max
Current
0/4…20mA 750Ω/10V max
Deviation threshold
Voltage
1-5/0-5/0-10V 500Ω/20mA max
Galvanic insulated
:
500 V
~~
/1min.
Resolution
: 12 bit (0.025%)
Accuracy
: 0.1%
. Short circuit protected
Local plus 2 stored Setpoints
Retransmission
of PV or SP
0…
range
Maximum slope
0.01…99.99%/s
up and down
Absolute threshold
Safety value
-100…100% .
(user enabled/disabled)
Related to the program (optional) (OP3)
Time proportioning
Relays
Band width
Heater Break detection
Triac
Action type
Acknowledge (latching)
SSR drive
NO 2A/250V
~~
resistive loads
Analogue
Current
Activation inhibit (blocking)
Voltage
Loop Break Alarm
Motor positioner (3 states)
Raise - Stop - Lower
Time programmable (optional)
SPST NO
, 2A/250V
~~
resistive load
Hysteresis
0.1…5.0%
symmetrical
Remote with trim
Local with trim
Local and Remote
Only Remote
Actions
Active high
Active low
0/4…20mA max 750Ω/10V max
Special
functions
0…22V–, 20mA max
(for static switches)
Double action
2 poles NO
, 2A/250V
~
resistive load
Ramp up and down, with slope in digit/s,
digit/minute or digit/hour
between
0.0…10.0%
of the range
High and low limits
M5 UK•ed4 10-12-2004 16:20 Pagina 41