Operating
voltage range
(Ambient
Temp.
<40 °C)
176 Vac ± 5 % @ 100 % - 50 % load;
110 Vac ± 5 % @ 50 % - 0 % load;
186 Vac ± 5 % @ 100 % - 50 % load;
120 Vac ± 5 % @ 50 % - 0 % load;
264 Vac ± 5 % @ 100 % - 50 % load;
300 Vac ± 5 % @ 50 % - 0 % load;
254 Vac ±5 % @ 100 % - 50 % load;
290Vac ± 5 % @ 50 % - 0 % load;
Operating frequency
range**
0.99 @ 100 % load (Nominal Input Voltage)
Bypass high voltage point
230-264: setting the high voltage point in LCD from
230 Vac to 264 Vac. (Default: 264 Vac)
Bypass low voltage point
170-220: setting the low voltage point in LCD from 170
Vac to 220 Vac. (Default: 170 Vac)
Line Mode
(synchroni
zed range)
Harmonic distortion (THDv)
≤ 3 % THD with linear load
≤ 5 % THD with non linear load