Questions and Answers

  • R
    robert85Aug 25, 2025
    What to do if my Astralpool Heat Pump shows a water flow failure TS1?
    • L
      Luis CohenAug 25, 2025
      If your Astralpool Heat Pump displays a water flow failure TS1, it could be due to a damaged water flow switch or insufficient water flow. Try replacing the water flow switch or checking the filtration pump and waterway system to ensure adequate water flow.
  • R
    Richard ThompsonAug 25, 2025
    Why is my Astralpool PRO ELYO INVERBOOST NN Heat Pump showing compressor current protection?
    • J
      Jason GrahamAug 26, 2025
      Compressor current protection in your Astralpool Heat Pump can occur due to several reasons: the compressor current being too large instantaneously, incorrect connection for compressor phase sequence, compressor accumulations of liquid and oil, a damaged compressor or driver board, abnormal water flow, or power fluctuations. To resolve this, check the compressor, compressor phase, power range, phase sequence connection, the waterway system and filtration pump, and mains power input.
  • M
    Michael SmithAug 26, 2025
    What causes T6 exhaust too high protection in Astralpool Heat Pump?
    • M
      martinmarkAug 27, 2025
      T6 exhaust too high protection in your Astralpool Heat Pump can result from a lack of gas, low water flow, a blocked piping system, or a faulty exhaust temperature sensor. Address this by checking the high-pressure gauge and filling with gas if needed, inspecting the waterway system and filtration pump, checking the piping system for blockages, and replacing the exhaust temperature sensor.
  • J
    Johnny RobersonAug 27, 2025
    What to do if my Astralpool PRO ELYO INVERBOOST NN Heat Pump displays a low pressure failure TS5?
    • J
      Joseph HarveyAug 27, 2025
      If your Astralpool Heat Pump is showing a low pressure failure TS5, it could be caused by a blocked EEV or jammed pipe system, abnormal motor speed or motor damage, or gas leakage. You should check the EEV and piping system, check the motor, use a high-pressure gauge to check the pressure value and check the refrigeration system.
  • C
    Cassandra WardAug 27, 2025
    How to fix communication failure between controller and main board in Astralpool Heat Pump?
    • H
      Hannah WilliamsAug 27, 2025
      A communication failure between the controller and main board of your Astralpool Heat Pump is often due to a poor signal wire connection, a damaged signal wire, or a controller malfunction. Check and reconnect the signal wire, replace the signal wire, turn off the electricity supply and restart the machine, or replace the controller.
  • J
    Jonathan BentleyAug 28, 2025
    What causes over heating protection for water temperature (T2) in heating mode in Astralpool PRO ELYO INVERBOOST NN Heat Pump?
    • S
      Susan HayesAug 28, 2025
      Overheating protection for water temperature (T2) in heating mode in your Astralpool Heat Pump can be triggered by low water flow, a stuck water flow switch cutting off water supply, or a faulty T2 sensor. Check the waterway system, the filtration pump or water flow switch, and the T2 sensor, replacing components as necessary.
  • M
    maria87Aug 29, 2025
    How to troubleshoot controller failure in Astralpool Heat Pump?
    • J
      jasonweberAug 29, 2025
      Controller failure in your Astralpool Heat Pump can stem from poor wire connections, damaged signal wires, or the controller itself failing. Try checking and reconnecting the signal wire, replacing the signal wire, turning off the electricity supply and restarting the machine, or replacing the controller.
  • J
    Julie HarrellAug 30, 2025
    What does 'T2 water temp. Too low protection under cooling mode' mean for my Astralpool PRO ELYO INVERBOOST NN Heat Pump?
    • A
      Antonio JimenezAug 30, 2025
      The 'T2 water temp. Too low protection under cooling mode' error in your Astralpool Heat Pump indicates either low water flow or a problem with the T2 temperature sensor. Check the filtration pump and waterway system or replace the T2 temperature sensor.
  • R
    roy88Aug 23, 2025
    What causes high pressure failure TS4 in Astralpool Heat Pump?
    • T
      Tiffany SmithAug 25, 2025
      High pressure failure TS4 in your Astralpool Heat Pump can be caused by several factors: the ambient temperature being too high, the water temperature being too high, low water flow, or an issue with the fan motor (abnormal speed or damage). To address this, check the water flow and filtration pump, inspect the fan motor, and examine and repair the piping system.
  • S
    Sarah BrewerAug 31, 2025
    What to do if my Astralpool Heat Pump shows VDC voltage too high protection?
    • T
      Tiffany LewisAug 31, 2025
      If your Astralpool Heat Pump shows a VDC voltage too high protection error, it indicates that the line voltage is too high or the driver board is damaged. Check if the power is in the normal range and change the driver board or main board.

Summary

3. Specifications

5. Location and connection

6. Electrical Wiring

6.1 Inverter swimming pool heat pump wiring diagram

Wiring diagram for inverter pool heat pumps (Models 71676/71677/71678/71679/71680).

6.2 Inverter swimming pool heat pump wiring diagram

Wiring diagram for inverter pool heat pumps (Model 71681).

6.3 Inverter swimming pool heat pump wiring diagram

Wiring diagram for inverter pool heat pumps (Models 71682/71683).

6.4 Inverter swimming pool heat pump wiring diagram

Wiring diagram for inverter pool heat pumps (Model 68822 (R410A)).

6.5 Inverter swimming pool heat pump wiring diagram

Wiring diagram for inverter pool heat pumps (Models 68821/68823 (R410A)).

6.6 Electrical connection

Guidelines and requirements for the electrical connection of the heat pump.

7. Start-up of the Heat Pump

7.3 Heating operation logic

Describes the logic and conditions for heating operation modes.

8. Troubleshooting

8.1 Error code display on LED wire controller

Lists error codes, their reasons, and solutions for LED wire controller displays.

8.2 Other Malfunctions and Solutions (No display on LED wire controller)

Troubleshooting guide for malfunctions not indicated by error codes on the controller.