Installation & Servicing instructions ATAG XL
21
Final discharge options.
Thecondensatepipecanonlyterminateintoanyoneoftheveareasasshowninthe
diagrams on this page.
Draining of the condensation water to the external rain guttering is not
permitted in view of the danger of freezing.
Before putting the boiler into operation ll the siphon with 600 ml of water.
A -Condensate from boiler siphon/trap
B -Sinkwithinternaloverow
C -25mm dia. Plastic condensate pipe
D -External drain or gully
E -Internal soil and vent stack.
F -Serviceable condensate trap (75mm min.)
G -300mm x 100mm dia. sealed plastic tube.
H -Ground level
J -Drainage holes facing away from the building
K -Lime stone chippings
L -Weather resistant insulation
Drain requirements gure 6.4.c