Installation & Servicing instructions ATAG XL
27
Forhorizontalsections,theoutletsystemshouldalwaysbettedonanincline(50mm/m)
sloping down towards the appliance so that no condensation water is able to accumulate
in the outlet system. The chances of icicles forming on the roof outlet is minimised
by causing the condensation water to run back towards the appliance. In the case of
horizontaloutletstheinletsystemshouldbettedonaninclineslopingdowntowards
the outside to prevent rainwater from coming in.
The appliance produces a white wisp of condensate (plumeing). This wisp of condensation
is harmless, but can be unattractive, particularly in the case of outlets in outside walls.
For wall terminals a plume management kit is available as an option.
Cutting the pipe goes as follows:
- Cutjustasmuchfromtheairintakepartasfromtheuegaspartusingahandsaw;
- Takeotheburrsfromthecuttingedgetopreventcuttingtheseals;
Whenmountingtheuegassystem,payattentiontotheowdirection(Seegure7.4.c).
It is not permitted to mount a system upside down and will lead to complaints.
Useasoapsolventorspecialgreasetosimplifythetting.
Refer to table 7.4.a for maximum applicable pipe length.
ø100mm
in m
XL70 Maximum straight lenth 100 63
87° bend resistance length -2,1
45° bend resistance length -2
XL110 Maximum straight lenth 100 35
87° bend resistance length -2,1
45° bend resistance length -2
XL140 Maximum straight lenth 100 12
87° bend resistance length -2,1
45° bend resistance length -2
ø100/150mm
B
in m
XL70 Maximum straight lenth 100/150 25
87° bend resistance length -1,7
45° bend resistance length -1,3
XL110 Maximum straight lenth 100/150 15
87° bend resistance length -1,7
45° bend resistance length -1,3
XL140 Maximum straight lenth 100/150 8
87° bend resistance length -1,7
45° bend resistance length -1,3
Two pipe flue system + chimney lining
Concentric flue system
Maximum ue length for individual ue gas outlet table 7.4.a
Example:
An XL70 with a
concentric ue gas system
ø100/150mm has according
to the table a maximum ue
straight length of 25m In the
system that is going to be put
in there are 2 x 45° bends, so
the maximum ue gas length
is
25 – ( 2 x -1.3) = 22.4
meters.
Flow direction Figure 7.4.c
Installation height Figure 7.4.b