PE6108AV / PE6208AV / PE8208AV User Manual
38
POP Setting Scenarios
Setting Description
A Triggers Proactive Overload Protection to power
off an outlet when it's Current Max Threshold
setting is exceeded. Only the outlet that exceeds
the threshold setting is powered off.
B Triggers setting A and:
Triggers Proactive Overload Protection to shut off
power to a newly inserted device (LIFO), when it
causes the PDU’s Aggregate Current Max
Threshold setting to be exceeded. Only the outlet
with a newly inserted device is powered off; all
other outlets stay on. If another outlet exceeds the
Aggregate Current threshold, an alarm is
triggered.
C Triggers setting A and:
Triggers Proactive Overload Protection when the
PDU’s Aggregate Current Max Threshold setting
is exceeded and shuts off power to the (LIFO)
outlet first, and then the remaining outlets in order,
according to the Bank POP Priority List. Any outlet
set to N/A will not be powered off.
D Triggers setting A and:
Triggers Proactive Overload Protection when the
PDU’s Aggregate Current Max Threshold setting
is exceeded to power off outlets according to the
Bank POP Priority List. Any outlet set to N/A will
not be powered off.