The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93 A
for a 50 mm² cable. For a cable of 70 mm², the maximum allowed current is 118 A,
which is sufficient. Therefore, use a 3 x 70 mm² + 35 mm² cable.
If method C is used, 50 mm² is suffficient. (35 mm² for method F) => cable 3 x 50 mm²
+ 25 mm².
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
I = (89 A + 10 %)/2 = (89 x 1.1)/2 = 49 A
For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So 2
parallel cables of 3 x 25 mm² + 25 mm² are sufficient.
Install 50 A fuses on each cable instead of 100 A.
Cable sizing according UL/cUL
Calculation method according UL 508A, table 28.1 column 5: allowable ampacities of insulated
copper conductors (75 °C (167 °F)).
Maximum allowed current in function of the wire size
AWG or kcmil Maximum current
10 < 30 A
8 < 50 A
6 < 65 A
4 < 85 A
3 < 100 A
2 < 115 A
1 < 130 A
1/0 < 150 A
2/0 < 175 A
3/0 < 200 A
Calculation method for UL:
Single supply cables (3 phases + 1 PE - configuration (1)):
Add 25 % to the total current from the tables (see UL 508A 28.3.2: "Ampacity shall
have 125 % of the full load current")
Install the prescribed maximum fuse on each cable
Parallel supply cable (2 x 3 phases + 2 PE - configuration (2)):
Add 25 % to the total current from the tables and divide by 2
Multiply the ampacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phase + 2 PE as in (3):
Add 25 % to the total current from the tables and divide by √3
Multiply the ampacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size PE cable:
For supply cables up to AWG8: same size as the supply cables
For supply cables larger than AWG8: use maximum allowed ampacity of the selected
supply cables and compare with value in table below (see CEC Part 1 table 17)