7.3.8 Low voltage (LV)
The "Low voltage" option allows to run the unit at low voltage
(= high current).
Q1......Circuit breaker for low voltage, high current
Interrupts the low voltage power supply towards X1 when a
short-circuit occurs at the load side or when the overcurrent
protection (QAS 80: 200 A, QAS 100: 250 A) is activated. It
must be reset manually after eliminating the problem.
7.3.9 Single phase (1 Ph)
The "Single phase" option provides single phase output voltage
(e.g. 230 V).
X1......Main power supply (230 V AC)
Terminals L1, L2, N (= neutral) and PE (= earthing), hidden
behind the control panel door and behind a small transparent
door.
Q1......Circuit breaker for single phase operation
Interrupts phases L1, L2 and N towards X1 when a short-
circuit occurs at the load side or when the overcurrent
protection is activated. It must be reset manually after
eliminating the problem.
7.3.10 Earth leakage relay
The “Earth relay” option provides a detector that will trip the main
circuit breaker Q1 when an earth fault current is detected.
Q1......Main circuit breaker
N13....Earth leak detector
Detects and indicates an earth fault current and activates the
main circuit breaker Q1. The detection level can be set at 0.03
A fixed with instantaneous trip but can also be adjusted
between 0.1 A and 1 A with time delayed (0 - 0.5 sec) trip. N13
has to be reset manually after eliminating the problem (reset
button marked R). It can be overridden by means of the earth
leak switch (S13, labelled IN) but has to be tested monthly
(by pushing test button T).
S13 ....Lock-out switch for earth fault protection (N13)
This switch is located inside the cubicle and is labelled IN.
Position O: No de-energising of the main circuit breaker Q1
when an earth fault occurs.
Position 1: De-energising of the main circuit breaker Q1 when
an earth fault occurs.
All the cables that are used must be suitable for high
current.
!
X1
Q1
X1
Q1
Q6
X1
X1
Q1
Position O will only be used in conjunction with an
external earth fault protection unit (e.g. integrated
in a distribution board).
If S13 is in position O, proper earthing is of the
utmost importance for the safety of the user.
Eliminating any earth fault protection can lead to
serious injury or even death for anybody touching
the unit or the load.