- 58 -
Battery under voltage / Battery over voltage The DC supply has fallen below or risen above the low/high volts setting level.
Generator under voltage
The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On
timer has expired.
Generator over voltage The generator output voltage has risen above the pre-set pre-alarm setting.
Under frequency
The generator output frequency has fallen below the pre-set pre-alarm setting after the Safety
On timer has expired.
Over frequency The generator output frequency has risen above the pre-set pre-alarm setting.
CAN ECU warning / CAN ECU shutdown
The engine ECU has detected an alarm – Check the engine light.
Contact the Engine Manufacturer for support.
CAN data fail
The module is configured for CAN operation and does not detect data on the engine CAN
datalink.
Emergency stop
The emergency stop button has been depressed. This is a failsafe (normally closed to battery
positive) input that will immediately stop the set, should the signal be removed.
Removal of the battery positive supply from the emergency stop input will also remove DC
supply from the Fuel and Start outputs of the controller.
The Emergency Stop positive signal must be present otherwise the unit will
shutdown.
Magnetic pickup failure Pulses are no longer being detected from the magnetic pickup probe.