Instruction book 
2920 1472 03    31 
 
4.  The inlet grids and ventilation fan should be installed in such a way that any recirculation of 
cooling air to the compressor is avoided.  The air velocity to the grids should be limited to 5 
m/s.  The required ventilation capacity (per compressor installed) to limit the compressor room 
temperature can be calculated as follows: 
 
  Qv  =  1.16 N / dT for ZT15 up to ZT22 
  Qv  =  (1.16 N + 3.2) / dT for ZT15 up to ZT22 Full-Feature 
  Qv  =  1.09 N / dT for ZT30 up to ZT45 
  Qv  =  (1.09 N + 5.5) / dT for ZT30 up to ZT45 Full-Feature 
  Qv  =  0.21 N / dT for ZR30 up to ZR45 
  Qv  =  (0.21 N + 5.5) / dT for ZR30 up to ZR45 Full-Feature 
 
Qv  =  required ventilation capacity in m³/s 
N  =  shaft input of the compressor in kW 
dT  =  temperature rise over ambient  
 
  If cooling air ducts are installed, the maximum allowable pressure drop over the ducts is 30 
Pa.  Common ducting for several compressors is not allowed. 
 
5.  Lay out the drain piping from automatic condensate outlets towards the condensate collector.  
The drain pipes must not dip into the water of the collector.  It is recommended to provide a 
funnel to allow visual inspection of the condensate flow. 
 
6.  Elektronikon control system with control panel. 
 
7.  See section 2.3 for the recommended cable size of the supply cables.  Check that the 
electrical connections correspond to the local codes.  The installation must be earthed and 
protected against short circuits by fuses in all phases.  An isolating switch must be installed 
near the compressor. 
 
8.  Provide a condensate drain valve in the lowest part of the pipe between the compressor outlet 
valve and the air net. 
 
9.  On ZT: optional main switch. 
 
9.  On ZR30 up to ZR45: position of cooling water pipes.  Remove the plastic plugs (if provided) 
from the compressor water pipes and connect the pipes to the cooling water circuit.  Provide a 
valve in the compressor water inlet pipe and outlet pipe.