Boilers do not reach their
required outputs and the pre-
set water temperatures
- insufficient chimney draught
- excessive chimney draught
- Bent blades of draught ven
-
tilator - ignition too long or
boiler operated with the igni
-
tion flap open
- insufficiently cleaned boiler
- combustion-air inlet to load
-
ing chamber is clogged
- new chimney; unsuitable con-
nection
- place a throttle valve (draught
limiter) in the flue-gas duct
- pull the draught regulator
pulling rod out
- straighten blades (to a 90°
angle)
- replace
- clean
- clean
doors leaking
- defective fibreglass cord
- the nozzle becomes clogged
- insufficient chimney draught
- replace
- adjust the door hinges
- do not burn small-particle
wood, sawdust, bark
- chimney defect
Ventilator does not turn
- boiler overheated – safety
thermostat fuse out
- rotating wheel clogged
- defective capacitor
- defective motor
- bad contact in plug of motor
cable lead
- press the thermostat push-but
-
ton (using a pencil)
- clean the ventilator including
the ducting from tar and sedi-
ments
- replace
- replace
- check - measure
36. Spares
Heatproof shaped piece – nozzle heatproof shaped piece /5/
Heatproof shaped piece /10/, /11/, /12/, /13/, /23/
Ventilator /4/
Switch with an indicator light /20/
Thermometer /18/
Control thermostat /24/
Safety thermostat /36/
Pump thermostat for DC15E /40/
Waste gas thermostat /35/
Door sealing cord 18 x 18 /26/
Door filling - Sibral /25/
Condenser for draught ventilator UCJ4C52 - 1µF /29/
Condenser for draught ventilator UCJ4C82 - 1,5µF /29/
Condenser for compressing ventilator KORA - 3µF (DC70S) /29/
Safety thermostat for 95°C pump (DC75SE) /7/
Switching thermostat for 70°C pump (DC75SE) /28/
Breaker /37/
CAUTIONfor boilers DC18S, DC22S, DC25S, DC20GS, DC22SX, DC25GS, DC30SE,
DC30SX use the draught ventilator UCJ4C52 with rotation wheel around Ø150 mm; for
boilers DC32GS, DC40GS, DC32S, DC50S, DC40SE, DC40SX use the draught ventila
-